|

Proper Ventilation
The second pillar of world class indoor air quality (IAQ) environments
is proper ventilation. The ASHRAE Standard 62-2001 offers two methods
of determining the amount of outdoor air required to properly ventilated
indoor occupied spaces for acceptable IAQ: the Ventilation Rate
Procedure and the IAQ Procedure. The Ventilation Rate Procedure
is described in Section 6.1 of ASHRAE Standard 62-2001. The IAQ
Procedure is described in Section 6.2 of the Standard. A brief description
of the ventilation Rate Procedure is given below. More details and
a description of the IAQ Procedure can be found by downloading the
Standard 62-2001. The following table from the Environmental Protection
Agency (EPA) is provided for reference.
|
Application
|
Occupancy
(people/1000 ft2 )
|
Outdoor Air Flow rate
(cfm/person)
|
| Offices |
|
|
| Office space |
7 |
20 |
| Reception areas |
60 |
15 |
| Telecom Centers |
60 |
20 |
| Conference rooms |
20 |
20 |
| Public Spaces |
|
|
| Corridors & Utilities |
- |
0.05 cfm/ft2 |
| Public restrooms |
- |
50 |
| Locker & dressing rooms |
- |
0.5 cfm/ft2 |
| Smoking Lounge |
70 |
60 |
| Elevators |
- |
1.0 cfm/ft2 |
Ventilation Rate Procedure
Step 1: Determine the quality of the outdoor air. The designer
cannot simply assume that the quality of the outdoor air surrounding
the building is acceptable for use as ventilation air. The "EPA
National Ambient-Air Quality Standards for Outdoor Air" tables
for particulate and gaseous contaminants should be referenced and
particulate and/or gaseous filtration is necessary if the threshold
levels for these contaminants are exceeded.
Step 2: If the outdoor air is unacceptable, the standard
advises that it be cleaned of filtered.
Step 3: Determine the amount of air required in each space
and install the appropriate HVAC system.
Section 6.1.3 of the ASHRAE Standard 62-2-1 states:
"Indoor air quality shall be considered if the required rates
of acceptable outdoor air in the table are provided for the occupied
space."
|